Assigner | siemens |
Reserved | 2023-10-20 |
Published | 2023-12-12 |
Updated | 2024-05-15 |
Description
A vulnerability has been identified in Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an improper input validation vulnerability that could allow an attacker to bring the service into a Denial-of-Service state by sending a specifically crafted message to 4004/tcp. The corresponding service is auto-restarted after the crash is detected by a watchdog.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C |
Problem types
CWE-20: Improper Input Validation
Product status
Any version before V2312
Any version before V4.1
Any version before V2.0 SP1
Any version before *
Any version before *
Any version before *
Any version before V17 Update 7
Any version before V18 Update 3
References
https://cert-portal.siemens.com/productcert/pdf/ssa-999588.pdf
https://cert-portal.siemens.com/productcert/html/ssa-999588.html